Click here to download the .pdf version of this blog with diagrams.
There are usually two different ways a compressor failure can happen.
- Mechanical failure of the IPR, valves, scroll or a bearing problem
- Electrical failure of the windings in the compressor
Before condemning a compressor for not starting these items must be confirmed.
- Voltage at the compressor on start up within 10% of nameplate
- Run capacitor checked and within tolerance
- Starting components checked and within tolerance
Checking windings using the Ohm meter
Disconnect wires C, Common, S, Start, and R, Run from the compressor terminals.
An Ohmmeter will typically give only a few readings techs are concerned with.
- An infinite amount of ohms OL indicates that there is not a path for current flow.
This OL reading is an indication of an Open.
- An Ohm reading with a number such as 30k or 35m states that there is some
resistance in the wire or coil (the resistive coil and current flow create the
magnetism needed for a motor to turn).
- C to S should have a higher Ohm reading than C to R because the Start winding is
a highly resistive winding. The reading between R and S should be equal to CS
plus CR.
- A 0 Ohm reading states that there is no resistance in a coil but there is a path for
current flow. This is an indicator of a short.
Checking Internal Pressure Relief Valve
The Internal Pressure Relief valve (IPR) for Copeland compressors will open if the
pressure differential (psi differential from suction to discharge) is too great.
For the R22 compressors the differential is typically 375 – 450 psi.
For the R410A compressors the differential is typically 550 – 625 psi.
The IPR will open when the differential becomes too great, and will reset (close) when
the pressure differential begins to equalize.
When it is open, the pressure may be the same on the high side as well as the low side
even though the compressor is running.
If this happens, turn the unit off and allow the pressures to stabilize. Turn the unit back
on and see if it has begun to pump properly.
If not, turn the system back off and install a temporary access port on hot gas line
approximately 6 inches from the compressor.
Restart the compressor
Connect liquid gauge to the hot gas line and then the liquid line, the readings should be
similar.
If the reading on the hot gas line is much higher than the liquid line, recheck for the
possibility of a restriction in the condenser coil.
Click here to download the .pdf version of this blog with diagrams.