Carbon Monoxide is a byproduct of incomplete combustion.
Forced air furnaces in use today typically develop a small amount of CO. This is then
vented up the flue and out of the residence.
For complete combustion, exact amounts of Fuel (Natural gas), Oxygen (combustion air),
and Heat (ignition source, flame temperature) are needed.
Altering these by adding more or providing less will generate incomplete
combustion. This incomplete combustion produces CO.
Causes of incomplete combustion
- Dirty burners
- Insufficient air or Excess fuel
- Poor mix of fuel and air - if oxygen does not come into
contact with all of the fuel, some of the fuel will be unburned.
- Insufficient temperature - a flame touching a cooler surface.
- Poor venting - products of combustion cannot get away from the combustion
process and are re-circulated back with combustion air.
Physical Properties of Carbon Monoxide
- Carbon monoxide is a highly toxic (poisonous) gas
- It is colorless, odorless, and tasteless
- Specific gravity is 0.980 – (slightly lighter than air)
- Disperses rapidly and evenly into the air in a house
- It is carried readily with convection air currents within the home
CO and the Human Body
- CO can kill humans and animals.
- Absorbed by the body through the lungs directly to the blood
- Binds with blood hemoglobin
- Displaces oxygen
- 242 times more attracted to blood cells than oxygen
- Restricts oxygen flow to the body’s vital organs
CO levels in the building
- OSHA maximum 50 ppm over 8 hours
- EPA maximum of 9 ppm over 24 hours
- Any reading of 5 ppm or greater should be an area of concern
CO levels in the flue pipe
- Consumer Product Safety Commission 400 ppm
- Typical maximum on start up 100 ppm
- Typical when running at steady state 20-50 ppm
Checking CO in the Flue
To check CO in the flue, drill a hole in the flue pipe approx 1 foot beyond the furnace
outlet.
Turn on the furnace and allow 5 minutes for the unit to reach a “steady state” condition.
“Steady state” means the unit has warmed up and the readings should become steady
at this point.
Now that the furnace is warm, cycle the unit off and then start the test.
- Follow manufacturer’s instructions for zeroing the meter
outdoors.
- Insert the aspirator tube into the vent pipe
- Cycle the furnace on
- After the burners ignite, and before the blower comes on start pumping the
aspirator.
- Note the readings while pumping approx 1 pump per second.
- The readings should fall steadily down to the 20-50 ppm range
- If the readings do not drop below 50 there is typically a problem with the
combustion process, i.e. too much or too little fuel, air, dirty burners, or venting
issues.
- Continue to pump after the blower comes on
- If the CO levels increase after the blower starts it is quite possible that air is
entering the chamber through a breach or a crack. Further inspection of the
chamber is required
The Carbon Monoxide limits in the vent pipe are 400 parts per million air-free.
This is a standard number, but in reality the modern systems rarely exceed 100 ppm.
Typically the readings in the flue pipe one foot or so from the flue outlet of the furnace
are in the 30-50 ppm range.
In the event that a systems readings fall outside of these parameters, the three basics of
combustion must be looked at again;
Fuel, Oxygen, and Heat.
Checking CO in the home
After zeroing the meter outdoors, remove the CO 205 aspirator
from the CO 220 detector. Walk through the home taking readings
on various levels. A home with smokers in it or a customer that
burns candles may have readings of 1-3ppm in the home.
While EPA sets the maximum of 9ppm over 24 hours, testing has
shown that levels of 5 ppm or greater should be investigated.